Hello, Sometimes, my cpu 1515f-2pn goes to “STOP” and I have this message in th log “Data corruption prior to sending to F-IO” The project is developped in Tia portal V16. Event ID : 16#0D:75D6 Thanks for help!
Hi Maesa & Yuwaris, Sorry for the late reply. the problem is solved. it was due to discrepancy fault. With best regards
Hi Maesa & Yuwaris,
Sorry for the late reply. the problem is solved.
it was due to discrepancy fault.
With best regards
See less
Hi, The safety program put your cpu to STOP. The data used to calculate your outputs in the safety program changed between start and end of your safety program (OB123). Please check this siemens guide: https://support.industry.siemens.com/cs/document/22099875/simatic-industrial-software-s7-distributRead more
Hi,
The safety program put your cpu to STOP.
The data used to calculate your outputs in the safety program changed between start and end of your safety program (OB123).
Please check this siemens guide:
https://support.industry.siemens.com/cs/document/22099875/simatic-industrial-software-s7-distributed-safety-configuring-and-programming?dti=0&lc=en-WW
In your error log I can see that the issue is with your %Q430.0 output.
Please check the network where your %Q430.0 output is writen. maybe the data (inputs and other data) used to calculate this output are changed in other tasks.
Best regards